BESS capacity, based on 3 units in parallel
Charge status level reserved exclusively for the UPS function
Continuous power output from the batteries in off-grid mode
Response Time in the Event of a Network Failure
The problem wasn’t the power available under normal conditions, but its instability: all it took was a brownout to shut down the entire nighttime harvesting cycle.
Technical Challenge
A suburban industrial area prone to frequent voltage drops (brownouts) and micro-outages, which cause standard charging stations to shut down and disrupt the nighttime cycles of the compactors.
Dogma treated electrical continuity as an integral part of the charging system, not as a separate issue: the BESS is not only used to charge vehicles, but also to protect them from grid instability.
BESS Sizing for UPS
Engineering of a Dogma Battery Box with three battery units connected in parallel, for a total of 645 kWh.
DCS Intelligence and SoC Reserve
The Dogma Control System mathematically reserves a portion of the charge level (20%), dedicating it exclusively to the UPS emergency function.
Seamless Transfer Procedure
When a network anomaly is detected, the DCS responds with a latency of less than 200 milliseconds to initiate a seamless transfer. The PCS switches to island mode, delivering up to 150 kW of continuous, pure power from the batteries: the vehicles complete the cycle without interruption or the need for manual restarts.